DN25, DN32 hydraulic switch
System components
All system components
The hydraulic separator is used to separate the heat source circuit and the heating circuit. It ensures that both circuits operate independently without the need to balance the currents.
The switch is empty inside, so that the flow is possible in all directions depending on the operating variant of the heating system. It also enables the heating medium to be flushed and vented.
Technical Data
DN25 | DN32 | |
material of the switch | Steel | |
Max. power (ΔT=20K) [kW] | 28 | 48 |
Max. flow [m /h] | 1.2 | 2 |
capacity [L] | 1.6 | |
EPP insulation | 30mm thickness | |
fastening | M8 | |
Dimensions [mm] (H/D/W) | 550/137/154 | |
Weight [kg | 4.4 | 4.5 |
Color | Black | |
DIMENSIONS OF THE FITTINGS AND CONNECTIONS | ||
1. Connection flow heat source | AG 1" | AG 5/4" |
2. Temperature sensor support | IG 1/2" | IG 1/2" |
3. Connection return heat source | GZ 1" | GZ 5/4" |
4. Drain valve support | IG 1/2" | IG 1/2" |
5. Connection Installation Return | AG 1" | AG 5/4" |
6. Connection Installation Flow | AG 1" | AG 5/4" |
7. Vent connection | IG 1/2" | IG 1/2" |